    您當前的位置:首頁 > 技術文章 > Common faults and causes of zirconia oxygen analyzers

    Common faults and causes of zirconia oxygen analyzers

    發(fā)布時間: 2024-12-13  點擊次數(shù): 1368次

    1. System maintenance.

    If the oxygen indicator shows zero or no oxygen indication in the oxygen quantity converter, first check whether the oxygen indication circuit open. If the circuit is normal, check whether the zirconia probe is normal. At a temperature of 700℃, measure the DC millolt value of the oxygen cell. If the potential is greater than 1 millivolt and the resistance is greater than 100Ω, it indicates the probe is aged and needs to be replaced with a sensor or probe. If the potential is less than 1 millivolt and the resistance is less than100Ω, it indicates an open circuit in the wiring, which should be checked and handled one by one.

    2. constant temperature system failure.

    (1) If the heating temperature cannot be maintained, check whether there is a short circuit or open circuit in the resistance wire inside the heating furnace The normal resistance of the heating furnace wire is about 60-80Ω. If the resistance wire is open or the resistance measured by the multimeter less than 60Ω, the heating furnace wire should be replaced.

    (2) When the converter shows that the temperature is too high or out of control, it not only causes inaccurate oxygen display but also acceler the aging or damage of the zirconia head. At this point, you should immediately check if the thermocouple is open-circuited, or a multimeter to check the thermocouple. If the resistance is greater than 20Ω, it is judged that the thermocouple is open-cuited, and the thermocouple and zirconia head should be replaced; another reason for the temperature失控is: relay or temperature control circuit failure, relay or temperature control circuit failure will cause the oxygen converter to always be in one of the heating voltages of the heating furnace, thus leading to an increase in.

    3. oxygen cell fault.

    (1) After the oxygen cell has been used for a period of time, the contact points of its leads may become oxidized, resulting in contact or detachment. This can cause the Em value (in units of a multimeter) to fluctuate and become unstable. Observe the oxygen cell and take action.

    (2) When the oxygen signal deviation is too large or inaccurate, it may be due to a short circuit in the zirconia electrode, which case the wiring of the zirconia cell should be checked for short circuits. When the temperature does not rise, if the internal resistance is less than 0Ω, it indicates a short circuit in the electrode, and the zirconia head needs to be replaced.

    (3) During the operation of the oxygen measurement device, if the background potential exceeds 10mV or is less than -30mV, it must be recalibrated. If the background potential remains abnormal after calibration, it indicates that the probe has aged and can no longer be used.

    4. pneumatic circuit failure.

    (1) The zirconia head is clogged with ash, causing an obstruction in the reference gas circulation. This results in a decrease in probe output potential Em and an increase in the background potential Eo. In this case, blowing several times with a bulb syringe at the gas inlet of the will resolve the issue after the gas line is unclogged.

    (2) Oxygen cell ash blockage: The probe should be removed from the ash blockage and the filter should be reinstalled.

    (3) Probe leakage has a significant impact on the probe.

    5. The oxygen content on both sides of the boiler is too high.

    By adjusting the boiler combustion conditions, when starting or stopping the boiler fan or coal mill group, if the oxygen content deviation on both sides of the boiler is large, it is a normal phenomenon. Once the boiler combustion conditions stabilize, the oxygen content display will return to normal. If the unit adjustment is not in place and the deviation is large on both sides, it is necessary to check if the zirconia head is working properly by dismantling the transmitter for inspection. The device requires the operator to adjust the gas flow. The gaseous and reference state gases should continuously flow through the electrode without stopping, and there should be no dead ends. However, too large a flow will have a cooling effect, making the cell temperature uneven and causing errors. If the flow is too small, it is not only easy to form stagnant gas flow and dead zones but also may cause local changes in oxygen concentration due to the conduction of oxygen ions, thus affecting the accuracy of the measurement and causing deviations on both sides.

    6. On-site interference causes failures.

    For newly installed instruments, due to the strong electromagnetic field, when an unstable fault occurs, the first thing to consider is the interference issue.


產(chǎn)品中心 Products
在線客服 聯(lián)系方式 二維碼

服務熱線

0550-2409223

掃一掃,關注我們

皖公網(wǎng)安備 34118102000850號

无码又爽又刺激a片涩涩动漫| 女人被爽到呻吟的视频动态图| 国产成av不卡在线观看| 日本不卡一区二区三区| 国产亚洲精品久久久久妲己| 天天av天天翘天天综合网| 兔费看少妇性l交大片免费| 国产成人91亚洲精品无| 一二三四社区在线高清观看| 99久久亚洲精品日本无码| 亚洲熟妇大图综合色区92| 少妇极品熟妇人妻高清性色av| 欧美激情一区二区三区在线| 欧美精品国产综合久久| 亚洲高肉动态图| 久久久国产精品人人片| 天天日天天老司机综合色| 在线视频免费观看| 精品少妇人妻av免费久久洗澡 | 女人扒开屁股桶爽30分钟| 亚洲国产精品色婷婷久久| 亚洲精品成人在线视频| 久久美女扒开尿口让我桶| 国产精品美女黄| 九九热这里都是精品国产| 亚洲一区二区三区无乱码| 国产精品成人av三级在线| 小sao货水好多真紧h无码视频| 日韩一区二区三区电影成人| 国产激情精品久久久一区| 国产精品第一国产精品| 国产成人精品亚洲777人妖| 99国产精品久久久久久久久久久| 欧美日本一区二区在线观看| 欧美巨大另类极品videosbest| 国产精品人人妻人人爽久久| 妖精视频欧美日韩国产精品 | 色呦呦视频网站在线观看| 国产免费又黄又爽又色毛| 97在线观看免费视频播放| 在线播放少妇被高潮不断|